Customization: | Available |
---|---|
After-sales Service: | Permanent |
Warranty: | 1years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
AC400V 100.33kW RLC Programmable Load Bank
1)Load test: Load the corresponding active power and reactive power within the rated value to test the load capacity of the inverter.
Product
|
AC400V-100.33kW RLC Programmable Load Bank |
Rating Voltage/Frequency |
Ac three-phase four-wire, line voltage AC400V(L-L)/50Hz,
Or single-phase AC230V(L-N)/50Hz;
|
Rated frequency | 50Hz, compatible with 60Hz |
Load connection mode |
Three-phase four-wire Y-type connection, with A, B, C, N a total of four terminals;
Three-phase three-wire Y-type connection, with A, B, C a total of three terminals;
Single-phase two-wire system can be connected to A, N; B, N; C or N.
|
Rated power AC400V/50Hz |
Resistance: 102.33kW, Inductive: 123.33kvar, capacitive: 102.33kvar |
Load Step |
Resistive load: Each phase gear is divided into: 0.001,0.002,0.002,0.005,0.01,0.02,0.02,0.05,0.1,0.2,0.2,0.5,1,1,2,2,2,5,10,10kW, the minimum step value is 0.001kW, each phase 34.11kW, the total of three phases is 102.33kW.
Inductive load: Each phase gear is divided into: 0.001,0.002,0.002,0.005,0.01,0.02,0.02,0.05,0.1,0.2,0.2,0.5,1,2,2,5,10,20kvar, the minimum step value is 0.001kvar, each 41.11 kvar, the three-phase total is 123.33 kvar.
Capacitive load: Each phase gear is divided into: 0.001,0.002,0.002,0.005,0.01,0.02,0.02,0.05,0.1,0.2,0.2,0.5,1,1,2,2,2,5,10,10kvar, minimum step value 0.001 kvar 34.11kvar per phase, The three phases add up to 102.33 kvar.
|
Power Factor | Adjustment range ±0.1-1, full load ±0.7-1. |
Load accuracy |
Resistance: cold ±3%, hot ±1.5%, combined ±3%
Capacitance: cold ±3%, hot ±0.1%, combined ±3%
Inductance: cold ±3%, hot ±0.1%, combined ±3%
|
Compatible voltage/frequency AC400V/60Hz |
When AC400V/60Hz:
Resistive (R) :102.33kW, inductive (L) : 102.77kvar, capacitive (C) : 122.79kvar.
|
Phase voltage measurement | The voltage measurement accuracy is ±0.2% and the voltage resolution is 0.1V |
Electric current measurement | The current measurement accuracy is ±0.2% and the current resolution is 0.1A |
Wattful power measurement | Power measurement accuracy is ±0.5%, power resolution is 0.001kW; |
Wattless power measurement | Power measurement accuracy is ±0.5%, power resolution is 0.001kvar; |
Working Mode | Continuous Working |
Transportation | Forklift or lifting |
Color | Gray RAL7035 |
Dimension | About 1500mm×1700mm×1800mm (L × W × H) |
Weight | About 1200kg |
Operating Environment Parameter | |
Work Temperature | -20ºC~+50ºC |
Relative Humidity | ≤95% |
Altitude | ≤2500M |
Atmospheric Pressure | 86~106kPa |