AC480V 3 phase 1100kW load banks
Technical Parameters | |
Rating Voltage/Frequency | AC480V 3 phase 4 wire ,50Hz/60Hz |
Compatible test voltage | Customers will use in the following voltage levels: Ac three-phase four-wire/three-phase three-wire, AC480V/50Hz/60Hz; Ac three-phase four-wire/three-phase three-wire, AC240V/50Hz/60Hz; Ac three-phase four-wire/three-phase three-wire, AC208V/50Hz/60Hz; Ac three-phase four-wire/three-phase three-wire, AC380V/50Hz/60Hz; Ac three-phase four-wire/three-phase three-wire, AC460V/50Hz/60Hz; Ac three-phase four-wire/three-phase three-wire, AC440V/50Hz/60Hz; Ac single-phase, AC240V/50Hz/60Hz; Ac single-phase, AC208V/50Hz/60Hz. |
Max Load Power | Resistive Load: 1100kW |
Load Step AC480V/60Hz | Resistive Load:total 15 steps:1,2,2,5,10,10,20,50,50,50,100,200,200,200,200kW When the input voltage is lower than the rated value, the load bank power changes according to Ohm's law. |
Power Factor | 1 |
Load Tolerance(each step) | ±5% |
Load Tolerance(overall) | ±3% |
Instrument display accuracy | Class 0.2 |
Control Power Supply | External AC three-phase five-wire AC480V/60Hz, about 12kW; |
Wire Connection | Load Power Supply Input--Copper row (star connection) Control power supply input--Terminal Block |
Communication Interface | RS485,RS232 |
Insulation Class | F |
Working | Continuous |
Cooling | Forced air cooling, side air in, side air out. |
Case construction | Air inlet and outlet, add protective net to prevent foreign bodies from entering. |
Transportation | Hoisting, the top of the chassis with a bearing ring, With casters and integrated forklift holes at the bottom. |
Color | Yellow color (RAL1023) |
Dimension | About 1820mm×1500mm×2270mm (L×W×H(including forklift hole, excluding casters, lifting ring height)) |
Weight | About 1500kg |
Remote console color | white bright, blue frame edge; |
Remote console | about 2700*1100*1500mm(width * depth * height); |
The remote console weighs | about 1600kg; |
Operating Environment Parameter | |
Work place | Outdoor; |
Temperature | -20ºC~+50ºC |
Relative Humidity | ≤95% |
Altitude | ≤2500m |
Atmospheric Pressure | 86~106kPa |
Function:
1. Control mode selection: The load can be controlled by selecting a local, remote, or intelligent mode.
2. Local control: through the switches and instruments on the local control panel, carry out the manual loading / unloading control of the load bank and view the test data.
3. Remote control:The system is equipped with a remote console for addition / load reduction control through the push button switch on the remote console.
4. intelligent control: With data processing software, could form curve of current, active power, reactive power, apparent power, power factor, frequency and can be printed.
5. Control mode interlock: there is switch in control panel to choose control mode, other control mode is invalid if user choose one control mode.
6. One-key load/ unload: using manual control or software control, preset the power value first, and then Starting master switch, the load bank will be loaded according to the preset value, so as to avoid the load fluctuation in the process of power adjustment.
7. Local meter display data: Parameters such as three-phase voltage, three-phase current, active power, reactive power, apparent power, power factor and other frequency can be displayed through the local measuring instrument.
8. Wire system switching: Through the local selection switch or the host computer software can choose the instrument wiring mode of load test, to achieve the switch of "three-phase three-wire" and "three-phase four-wire", single-phase test, the use of "three-phase four-wire" connection, the main loop is connected to L1-N.
Protection: Emergency Stop; Over voltage Protection; Short Circuit Protection; Overheating Protection; Fan Interlock Protection;
Fan Delivery Protection; Phase Sequence Protection of Fans; Protection Buttons; Chassis Grounded Protection
If you have customization needs or would like to know more product details, please send me an inquiry
1. Kaixiang is the largest and earliest load bank manufacturer in China, we have 30 years experience. Our factory has 25,000 square meters.
2. The sole company that draw up the enterprise standard "Dry-type load bank" in China.
3. As the sole load bank supplier for China nuclear field and the largest load bank supplier for marine and aviation industry.
4. China Power Industry Top Ten Famous Products.
5. China Power Supply Recommend Products.
6. Certified by SGS, CE, ISO9001:2008.
7. Public company, as listed company in 2015.
Hebei Kaixiang Electrical Technology Co., Ltd is the largest and earliest load bank manufacturer in China, we have 30 years experience.