Customization: | Available |
---|---|
After-sales Service: | Permanent |
Warranty: | 1years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
AC11kV-5000kW Load Bank
1)Control and Display: Load testing, local control (buttons), intelligent control, control interlock, one-key addition and reduction of load, local instrument display of data.
Product
|
AC11kV-5000kW Intelligent Load Bank |
Rating Voltage/Frequency | AC 3-phase 3-wire AC11kV 50Hz/60Hz |
Max Load Power | Resistive power: 5000kW |
Load Step |
Resistive load: divided into 8 levels, They are: 200,400,400,500,500,1000,1000,1000kW
Instructions:
When the access voltage is lower than the rated voltage, the power of the load cabinet gear changes according to Ohm's law.
|
Load Tolerance(each gear) | ±3% |
Load Tolerance (overall) | ±3% |
Working Power | 3 phase 5 wire External (A/B/C/N/PE)AC380V /50Hz About 85kw |
Maximum protection class | Control part IP56, alloy resistance power dissipation chamber IP21. |
Wire Connection |
Load Power Supply Input--Busbar (star connection) Control power supply input--Terminal block Use side or bottom access test cable, working power supply and remote control cable |
Insulation Class | F |
Level of protection | Overall IP54, power part IP21 when the tuyere is open, other IP54 |
Construction | Container packaging, the box is equipped with personnel access door, and locked, Equipped with ladder access to the top, inlet/outlet wind protection door, A protective net is added inside to prevent foreign bodies from entering. |
Communication Interface | RS485,RS232 |
Working Mode | Continuous Working |
Cooling | Forced air cooling, side air inlet, The top of the chassis is ventilated |
Transportation | Hoisting, the top of the chassis with load-bearing rings, in line with lifting and transportation conditions. |
Chassis structure |
Container packaging, the box is equipped with personnel access door, and locked,
It is equipped with a ladder that can reach the top, air inlet protection door, shutter configuration, and internal protective net to prevent foreign bodies from entering.
|
Color | Grey (RAL7035) |
Dimension | About 12192mm×2350mm×2591mm (L × W × H) |
Weight | About 11300kg |
Operating Environment Parameter | |
Work Temperature | -20ºC~+50ºC |
Relative Humidity | ≤95% |
Altitude | ≤2500M |
Atmospheric Pressure | 86~106kPa |