AC415V 3 phase 200kW load banks
Technical Parameters | |
Rating Voltage/Frequency | AC 415V/50Hz, 3 phase 4 wire |
Max Load Power | Resistive Load: 200kW |
Load Step | Resistive Load.9 steps;1,2,2,5,10,10,20,50,100kW. Instructions: When the input voltage is lower than the rated voltage, the power of the load cabinet gear changes according to Ohm's law. |
Power Factor | 1 |
Load Tolerance(each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display accuracy | Grade 0.5 |
Working Power Source | Optional internal and external AC single-phase (L/N/ PE) AC240V/50Hz, about 2kW; |
Electrical outlet | Install a 15A waterproof Australian socket on the outside of the case, Connect to the back end of the internal and external power supply |
Wire Connection | Load power input -- copper bar (star connection), Control power input - wiring bar; |
Insulation Class | F |
Case material | 304 Stainless steel; |
Maximum protection level | IP34; |
Working Mode | Continuous Working |
Cooling | Forced air cooling,Horizontal inlet air,Horizontal outlet |
Transportation | Hoisting: The chassis is provided with load-bearing rings at the top and casters at the bottom |
Color | White orange pattern; |
Dimension | About 1040mm×1450mm×1200mm(L*W*H); |
Weight | About 250kg; |
Operating Environment Parameter | |
Site | Outdoor, Weatherproof |
Ambient Temperature | -10ºC~+50ºC |
Relative Humidity | ≤95% |
Altitude | ≤2500 meters |
Atmospheric Pressure | 86~106kPa |
1. Load testing: can load any power within the rated value, measure and display voltage, current, active power, reactive power, apparent power, power factor, frequency and other parameters.
2. Control Pattern: The load is controlled locally
3. Local Control: The load is equipped with a local control panel and divided into a number of power gears, which can be controlled through the gear switch.
4. Local instrument: The local instrument can display voltage, current, active power, reactive power, apparent power, power factor, frequency and other parameters.
5. Cable and indicator requirements: L1 red line, L2 white line, L3 blue line, N black line, PE yellow-green [Each color of the line must be the whole color of red, white, blue and black, not just the end of the corresponding line color requirements]
Protection:Emergency Stop; Over voltage Protection; Short Circuit Protection; Overheating Protection; Fan Interlock Protection; Protection Buttons; Chassis Grounded Protection
If you have customization needs or would like to know more product details, please send me an inquiry
1. Kaixiang is the largest and earliest load bank manufacturer in China, we have 30 years experience. Our factory has 25,000 square meters.
2. The sole company that draw up the enterprise standard "Dry-type load bank" in China.
3. As the sole load bank supplier for China nuclear field and the largest load bank supplier for marine and aviation industry.
4. China Power Industry Top Ten Famous Products.
5. China Power Supply Recommend Products.
6. Certified by SGS, CE, ISO9001:2008.
7. Public company, as listed company in 2015.
Partners
Company Information
Hebei Kaixiang Electrical Technology Co., Ltd is the largest and earliest load bank manufacturer in China, we have 30 years experience.