ACT400V 3 phase 100kW load banks
Technical Parameters | |
Rating Voltage/Frequency | AC three-phase three-line 400V 50 / 60Hz (no zero line) |
Max Load Power | Resistive Load:100kW |
Load Step (AC400V/50Hz) |
Resistive Load:8 ,1,2,2,5,10,20,20,40kW When the input voltage is lower than the rated value, the load bank power changes according to Ohm's law. |
Power Factor | 1 |
Load Tolerance (overall) | ±3% |
Display precision | Class 0.5 |
Control Power Supply | External AC110-240V Single Phase 50/60Hz,About 1kW |
Wire Connection | Load power input -- fast plug (domestic rhinoceros socket); Control the power input -- three-core power socket. |
Communication Interface | RS485 |
Insulation Class | F |
Working Mode | Continuous Working |
Cooling | Forced air cooing, horizontal inlet and outlet |
Color | White |
Transport or move | Haft |
Dimension | About 540mm×292mm×582mm(L*W*H) |
Weight | About 35kg |
Operating Environment Parameter | |
Work Place | Indoor |
Work Temperature | -20ºC~+50ºC |
Relative Humidity | ≤95% |
Altitude | ≤2500M |
Atmospheric Pressure | 86~106kPa |
Ventilation distance | The air inlet is required to be 1 ~ 2 meters free of obstacles. High temperature of air outlet, obstacle more than 3 meters. |
Safe working distance | There should be an isolation fence 1 meter away from the load cabinet. When the load cabinet is working, there should be no idle personnel within 3-5 meters. |
Function:
1. Load test: any power within the rated value can be loaded to measure and display the steady-state three-phase current, active power, power factor, frequency, operating time and other parameters.
2.Control mode: user can choose local manual control , or Intelligent control(PC control).
3. Local control: through the switches and instruments on the local control panel, carry out the manual loading / unloading control of the load bank and view the test data.
4. Intelligent control: With data processing software, could form curve of current, active power, reactive power, apparent power, power factor, frequency and can be printed.
5. Control mode interlock: there is switch in control panel to choose control mode, other control mode is invalid if user choose one control mode.
6. One-key load/ unload: using manual control or software control, preset the power value first, and then Starting master switch, the load bank will be loaded according to the preset value, so as to avoid the load fluctuation in the process of power adjustment.
7. Data display: it could display Three phase voltage, three-phase current, active power, reactive power, apparent power, power factor, frequency and other parameters.
Protection:Emergency Stop; Over voltage Protection; Overheating Protection; Fan Interlock Protection; Chassis Grounded Protection
If you have customization needs or would like to know more product details, please send me an inquiry
1. Kaixiang is the largest and earliest load bank manufacturer in China, we have 30 years experience. Our factory has 25,000 square meters.
2. The sole company that draw up the enterprise standard "Dry-type load bank" in China.
3. As the sole load bank supplier for China nuclear field and the largest load bank supplier for marine and aviation industry.
4. China Power Industry Top Ten Famous Products.
5. China Power Supply Recommend Products.
6. Certified by SGS, CE, ISO9001:2008.
7. Public company, as listed company in 2015.
Partners
Company Information
Hebei Kaixiang Electrical Technology Co., Ltd is the largest and earliest load bank manufacturer in China, we have 30 years experience.