Customization: | Available |
---|---|
Warranty: | 12 Months |
Type: | Load Bank |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
AC400V 100KW Portable Intelligent ACT Power Test Load Bank for Generator
Technical Parameters | |
Rating Voltage/Frequency | AC400V 3 Phase 4 Wire /50Hz/60Hz |
Max Load Power | Resistive Load:100kW |
Load Step (AC400V/50Hz) |
Resistive Load:8 ,1,2,2,5,10,20,20,40kW When the input voltage is lower than the rated value, the load bank power changes according to Ohm's law. |
Power Factor | 1 |
Three-phase unbalance | ≤3% |
Load Tolerance (overall) | ±3% |
Display precision | Class 0.5 |
Control Power Supply | External AC110-240V Single Phase 50/60Hz, About 2kW |
Wire Connection | Load bank input--Busbar (star coupling ) Control power input--3-pin socket |
Communication Interface | RS485 |
Insulation Class | F |
Working Mode | Continuous Working |
Cooling | Forced air cooling, side inlet air, side outlet air. |
Color | White oxide |
Transport or move | Handle |
Dimension | About 544mm×292mm×584mm(L*W*H) |
Weight | About 35kg |
Operating Environment Parameter | |
Work Place | Indoor |
Work Temperature | -20ºC~+50ºC |
Relative Humidity | ≤95% |
Altitude | ≤2500M |
Atmospheric Pressure | 86~106kPa |
Ventilation distance | The air inlet is required to be 1 ~ 2 meters free of obstacles. High temperature of air outlet, obstacle more than 3 meters. |
Safe working distance | There should be an isolation fence 1 meter away from the load bank. When the load cabinet is working, there should be no idle personnel within 3-5 meters. |
Function:
1. Control mode selection: you can choose the local or intelligent mode to control the load.
2. Local Control: There is local control panel with several power steps; user can load/unload by button.
3. Intelligent Control: Through data processing software in PC, user can make automatic load, to display, rcord and manage the testing data, to form curves, tables, also to print them.
4. Control mode Interlock: there is control pattern switch, when choose one control pattern, operation of other pattern is invalid, avoid the clash.
5. Load/unload with One Key: Whether manual control, remote control or software control, user can preset the power, then press load master button. Load bank loaded according to preset power to avoid load fluctuation during the power changing.
6. Local Meter Display Data: Three-phase voltage, three-phase voltage, active power, reactive power, apparent power, power factor and frequency parameters can be displayed through the local measuring instrument.
Protection:Emergency Stop; Over voltage Protection; Overheating Protection; Fan Interlock Protection; Chassis Grounded Protection
If you have customization needs or would like to know more product details, please send me an inquiry
1. Kaixiang is the largest and earliest load bank manufacturer in China, we have 30 years experience. Our factory has 25,000 square meters.
2. The sole company that draw up the enterprise standard "Dry-type load bank" in China.
3. As the sole load bank supplier for China nuclear field and the largest load bank supplier for marine and aviation industry.
4. China Power Industry Top Ten Famous Products.
5. China Power Supply Recommend Products.
6. Certified by SGS, CE, ISO9001:2008.
7. Public company, as listed company in 2015.
Partners
Company Information