Customization: | Available |
---|---|
Application: | Electrical & Electronics |
Power Factor: | 1 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Technical Parameters | |
Rated Voltage /Frequency |
Ac three-phase three wire, AC220V and AC440V; 60Hz, compatible with 50Hz; |
Max Load Power | 200kW |
Load Step AC400V/50Hz |
Resistive load: divided into 9 gears, Respectively: 1,2,2,5,10,10,20,50,100 kW. 1,440 V/220V dual voltage switching, both meet 200kW; 2, lower than the rated voltage when the gear power according to Ohm's law decline. |
Power Factor | 1 |
Load Tolerance (each step) | ±5% |
Load Tolerance (overall) | ±3% |
Display Precision | 0.5 class |
Control Power Supply | External AC three-phase four-wire (L1/L2/L3/N) AC230V/60Hz. |
Wire Connection | Load bank input--Copper row (angle-type connection method); Control power input--terminal block |
Communication Interface | RS232/ RS485 |
Insulation Class | F Class |
Working Mode | Continuous Working |
Cooling | Forced air cooling, horizontal inlet and outlet,Air inlet and outlet with louvered frame and plate |
Transportation | With lifting eyes and wheel castors and forklift at bottom. |
Casing Color | white. |
Dimension | About 1620mm×1400mm×1190mm (long × wide × High, excluding the height of casters and lifting rings) |
Weight | About 500kg |
Operating Environment Parameter | |
Workplace | Outdoor |
Work Temperature | -20ºC~+50ºC |
Relative Humidity | ≤95% |
Altitude | ≤2500M |
Atmospheric Pressure | 86~106kPa |
Why choose us
1. Professional technical team with more than 20 years design experience.
2. Customized technical solutions meet customer's individual requirements.
3. Strict inspection procedures throughout the whole production flow.
4. Perfect after sales service create good user experience.
5. Reliable quality & competitive price maximize profits for customers.
6. Certified with CCS and ISO9001:2008 Quality Certificate.