Customization: | Available |
---|---|
After-sales Service: | 3months-1year |
Application: | Electrical & Electronics |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Technical Parameter | |
Rating voltage/frequency | AC three-phase four wire 400V-50Hz Compatible with 60Hz |
Max Load Power | Resistance Load:610kW |
Load Steps (AC400V/ 50Hz) |
Resistive Load: 11 steps,1,2,2,5,10,20,20,50,100,200,200kW Instructions: When the input voltage is lower than the rated voltage, the power of the load cabinet gear changes according to Ohm's law |
Power Factor | 1 |
Load accuracy (per gear) |
±5% |
Load Tolerance (overall) | ±3% |
Display Meter | 0.5 |
Fan Control Power | External AC three-phase five-line (A / B / C / N / ground) AC380~400V / 50Hz, about 8kW. |
Wire Connection | Load bank input--Copper bar (star connection); Control power input--Connector bar |
Communication Interface | RS485,RS232, |
Insulation | F |
Way of Working | Continuous Working |
Cooling | Forced air cooling, side inlet, upper outlet. |
Transportation | For hoisting, there are load bearing rings at the top of the chassis and casters at the bottom and forklift orifice |
Color | Black border + Dark blue (RAL5002) |
Dimensions | About 1650mm×1350mm×1680mm((L × W × H ) |
weight | About 900kg |
Operating Environment Parameter | |
workplace | indoor; |
Ambient Temperature | -20ºC~+50ºC |
Work noise | 1 meter away from the equipment: ≤85dB; |
Relative Humidity | ≤95% |
Altitude | ≤2500 meters |
Atmospheric Pressure | 86~106kPa |