Customization: | Available |
---|---|
After-sales Service: | Permanent |
Warranty: | 1years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
AC400V 60.33kW RLC Programmable Load Bank
1)Load test: Load the corresponding active power and reactive power within the rated value to test the load capacity of the inverter.
Product
|
AC400V-60.33kW RLC Programmable Load Bank |
Rating Voltage/Frequency |
Ac three-phase four-wire, line voltage AC400V(L-L)/50Hz,
Or single-phase AC230V(L-N)/50Hz;
|
Rated frequency | 50Hz, compatible with 60Hz |
Load connection mode |
Three-phase four-wire Y-type connection, with A, B, C, N a total of four terminals;
Single-phase two-wire system can be connected to A, N; B, N; C or N.
|
Rated power AC400V/50Hz |
Resistance: 60.33kW, Inductive: 72.33kvar, capacitive: 60.33kvar |
Load Step |
Resistive load: Each phase gear is divided into: 0.001, 0.002, 0.002, 0.005, 0.01, 0.02, 0.02, 0.05, 0.1, 0.2, 0.2, 0.5, 1, 1, 2, 5, 10kW, the minimum step value is 0.001kW, each phase 20.11kW, the total of three phases is 60.33kW.
Inductive load: Each phase gear is divided into: 0.001, 0.002, 0.002, 0.005, 0.01, 0.02, 0.02, 0.05, 0.1, 0.2, 0.2, 0.5, 1, 2, 2, 3, 5, 10kvar, the minimum step value is 0.001kvar, each 24.11 kvar, the three-phase total is 72.33 kvar.
Capacitive load: Each phase gear is divided into: 0.001, 0.002, 0.002, 0.005, 0.01, 0.02, 0.02, 0.05, 0.1, 0.2, 0.2, 0.5, 1, 1, 2, 5, 10 kvar, minimum step value 0.001 kvar, 20.11kvar per phase, The three phases add up to 60.33 kvar.
|
Power Factor | Adjustment range ±0.1-1, full load ±0.7-1. |
Load accuracy |
Resistance: cold ±3%, hot ±1.5%, combined ±3%
Capacitance: cold ±3%, hot ±0.1%, combined ±3%
Inductance: cold ±3%, hot ±0.1%, combined ±3%
|
Compatible voltage/frequency AC400V/60Hz |
When AC400V/60Hz:
Resistive (R) :60.33kW, inductive (L) : 60.28kvar, capacitive (C) : 72.4kvar.
|
Phase voltage measurement | The voltage measurement accuracy is ±0.2% and the voltage resolution is 0.1V |
Electric current measurement | The current measurement accuracy is ±0.2% and the current resolution is 0.1A |
Wattful power measurement | Power measurement accuracy is ±0.5%, power resolution is 0.001kW; |
Wattless power measurement | Power measurement accuracy is ±0.5%, power resolution is 0.001kvar; |
Control power supply | External AC single-phase (L/N/ ground)AC220V/50Hz, about 2kW. |
Wire Connection | Three-phase four-wire star connection, There are A, B, C, N four wiring ports; |
Transportation | Forklift or lifting |
Color | Gray RAL7035 |
Dimension | About 1500mm×1700mm×1800mm (L × W × H) |
Operating Environment Parameter | |
Work Temperature | -20ºC~+50ºC |
Relative Humidity | ≤95% |
Altitude | ≤2500M |