Customization: | Available |
---|---|
Application: | Electrical & Electronics |
Certificate: | ISO CE |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1100kw Resistive Load Bank for Generator Test with Affordable Price
Main functions:
1. Users can set adjustable load power within rated power.
2. Current, voltage, frequency, power factor, and active power, reactive power, and apparent power can be displayed.
3. With software programmable control, graphs of current, voltage, frequency, power factor, power can be displayed, saved and printed.
Control mode: manual control (control panel) with remote controller box or PC control.
Display meters: multi-function digital meter or generator tester.
Protection: Over load protection, over heat protection, short circuit protection, Emergency stops switch, etc
Technical Parameters |
|
Rating Voltage/Frequency |
415VAC, 3 phase 3 wire, 50Hz /60Hz |
Max Load Power |
Resistive Load:1100kW |
Load Step (AC415V/50/60Hz) |
Resistive Load:1,2,2,5,10,10,20,50,100,100,200,200,200,200kW Note: When the input voltage is lower than the rated voltage, the step power of the load bank changes according to Ohm's law. |
Power Factor |
1 |
Load Tolerance (each step) |
±5% |
Load Tolerance (overall) |
±3% |
Display Precision |
0.5 class |
Control Power Supply |
Internal & External 400VAC,50/60Hz, 3 phase 3wire + Ground,about 12kW Marks:When connected internally, the instrument displays the electrical parameters of the working power supply |
Wire Connection |
Load power supply input--Copper bar with at least 4holes (hole dia. 240mm2) (star coupling) Control power supply input--Connector-bar |
Communication Interface |
RS485,RS232 |
Insulation Class |
F Class |
Working Mode |
Continuous Working |
Cooling |
Force air cooling, horizontal air inlet and vertical air outlet |
Transportation |
Hoisting, there are lifting lug on top and castors at the bottom of casing |
Casing Color |
Grey(RAL7035) |
Dimension |
About 2660mm×1400mm×1680mm(L*W*H) |
Weight |
About 1200kg |
Operating Environment Parameter |
|
Workplace |
Outdoor |
Work Temperature |
-20ºC~+50ºC |
Working noise |
1m from the equipment |
Relative Humidity |
≤95% |
Altitude |
≤2500m |
Atmospheric Pressure |
86~106kPa |
Main Components Brands |
|
Contactor |
Schneider |
Fuse |
Miro |
PLC control module |
Siemens |
Alloy resistance |
Kaixiang (self-developed) |
Data management software |
Kaixiang (self-developed) |
Certificate and qualification
Company introduction
Hebei Kaixiang Electrical Technology Co., Ltd is a leading manufacturer in emergency power supply test & maintenance industry. Specialized in the design, R&D, manufacture of the high capacity AC & DC load bank, it owns the largest intelligent power supply testing equipment R & D centre in China.
The company's core technologies are independent research. there are seven patents, ten software copyrights and two corporate standards. It has been named the international advanced level scientific and technological achievements by Science and Technology Department of Hebei Province.
Kaixiang offer one-stop solutions to generator set & battery & UPS power manufacturers. Its products are widely used in data centre, shipbuilding, offshore platform, state grid, nuclear power, hospital, communication, railway, war industry etc filed. Kaixiang is strategy partner of many famous company, such as Cummins, Caterpillar, Kohler, Jiangnan Shipyard, CSSC,CSIC, State grid, China mobile, Tecent, Baidu, Sinopec, CETC etc. Some of its products have been exported to America, Singapore, Israel, Japan, United Kingdom, Saudi Arabia, Australia, South Korea, Thailand, Sri Lanka, Angola etc. Through years of development, "Triumph Load" already the first brand in power supply detection industry in China.
Company structure
Our Services
Exihibition hall
Application
Large generator system testing in ocean engineering, drilling facilities,ship construction etc
Factory testing for generator, static voltage characteristic test, speed characteristic test;
Marine generator overload protection test,parallel operation test,reverse power and reverse
current protection test
Assist shipyard in mooring test,sea trial test
Assist with the acceptance of the vessel generator test
Eliminate the carbon deposition of generator
As the generator loading system
Periodic running test for standby generator
UPS inspection and maintenance
Ship battery charging/discharging system testing
The acceptance of new system and testing of servicing equipment
To reduce "wet stacking" problems